Smart Leader

LOW TEMPERATURE THERMOVENTILATION

LOW TEMPERATURE CENTRIFUGAL FAN THERMOVENTILATION FOR HEATING IN THE "H" VERSION AND COOLING IN THE "C" VERSION

 

The SMART LEADER fan heaters have been sized to meet the eligibility criteria of the thermal account “Italian Ministerial Decree 16 February 2016 Annex 1" (Operation with medium fluid temperature <45°C).
The range consists of 6 models of which 4 relate to heating only and 2 relate to heating and cooling.
The SMART LEADER 35 C - 55 HP version was specifically designed to be directly combined with HEAT PUMP heat pump systems.

 

  • It can be combined with systems such as HEAT PUMP (Model 35 C - 55 HP), optimising performance via operation with the carrier fluid supply = 38°C min.
  • Operation also with average temperatures of the carrier fluid <45°C (Italian Ministerial Decree 16/02/2016 ann. 1)
  • It optimises the performance of condensing boilers
  • Steel load-bearing structure
  • IP 54 degree of electrical protection
  • Casing in ABS and steel, (stainless steel optional)
  • Standard air filter, (high surface area)
  • Centrifugal fan with variable flow rate, (3 speeds)
  • High air flow rates
  • Adjustable horizontal fins
  • Finned coil in copper and aluminium
  • Condensate collection tray (version C)
  • Possibility of combining with Energy Saving, to control the air delivery temperature according to environmental comfort (optional)

INSTALLATION EXAMPLES

Models available

SMART LEADER 30H

THERMAL PERFORMANCE

SMART LEADER 45H

THERMAL PERFORMANCE

SMART LEADER 35H

THERMAL PERFORMANCE

SMART LEADER 35C-50H

THERMAL PERFORMANCE

SMART LEADER 40H

THERMAL PERFORMANCE

SMART LEADER 35C-55HP

THERMAL PERFORMANCE

SMARTLEADER MODELS

 

 

30

35

 40

45

 35C - 50H

 35C - 55HP

  Risc. Risc. Risc. Risc. Raff. Risc. Raff. Risc.

TERMAL AND/OR COOLING CAPACITY

TOT.

kW

33,33

38,7

42,8

46

35,4

48,6

35,4

54,6

SENSIB.

kW

-

-

-

-

24,7

-

24,7

-

FEED WATER TEMPERATURE

IN

°C

50

50

50

50

7

50

7

54

OUT

°C

25

30

35

40

12

45

12

49

MAX VENTILATION AIR FLOW

OUT

m3/h

5.139

5.195

 5.237

5.268

4.553

5.295

4.553

5.356

RESIDUAL AIR VENTILATION PRESSURE

 

UR%

50

50

50

50

50

50

50

50

SUPPLY AIR TEMPERATURE

 

°C

36,4

39,8

42,3

44,2

10,6

45,8

10,6

49,5

RELATIVE HUMIDITY OF THE OUTLET AIR

 

UR%

-

-

-

-

96,6

-

96,6

-

RESIDUAL AIR VENTILATION PRESSURE

 

Pa

31

31

31

31

10

31

10

31

SUPPLY H2O FLOW RATE

 

Litri/h

1150

1680

2480

4000

6070

8460

6070

9520

PRESSURE LOSS ON THE H2O SIDE

 

kPa

5

9

16

34

85

125

85

152

OVERALL DIMENSIONS

H

mm

1.371

1.371

1.371

1.371

1.371

1.371

L

mm

1.200

1.200

1.200

1.200

1.200

1.200

P

mm

814

814

814

814

814

814

NUMBER OF FANS

 

1

1

1

1

1

1

ELECTRIC POWER SUPPLY

 

V/Hz

230/50

230/50

230/50

230/50

230/50

230/50

ELECTRIC POWER

 

W

1.200

1.200

1.200

1.200

1.200

1.200

WEIGHT

 

kg

150

150

150

150

150

150

MAX WORKING SPEED H20

25

20

15

10

5

5

5

5

WINTER ENVIRONMENT

16

16

16

16

16

-

16

-

SUMMER ENVIRONMENT

-

-

-

-

-

26

-